TECHNICAL PAPER



         table 2: Details of column specimens

           tYpE of      no. of    dEsIgnatIon                   sIzE of spEcImEns     slEndErnEss       tYpE of
          column      spEcImEns                    % ra                                  ratIo      rEhaBIlItatIon
                                                               hEIght     dIamEtEr
                                                               (mm)         (mm)
          Type 1                       C1            0          700          250                          Nil
                          3            S1           100         700          250           2.8        Strengthening
                                       R1           100         700          250                        Repairing
          Type 2                       C2            0          1200         250                          Nil
                          3            S2           100         1200         250           4.8        Strengthening
                                       R2           100         1200         250                        Repairing


         The behaviour of circular columns subjected to axial loading is   The compressive strength and modulus of rupture values of test
         to be studied. The testing was carried out in the loading frame   specimens are shown in Table 3. From this table, it is clear that
         and the compressive load was applied with the hydraulic loading   both compressive as well as modulus of rupture of specimens
         jack of capacity 750 kN. Concentric compressive load was   tend to decrease with increase in % of RCA.
         applied on all the specimens. Lateral deflections were measured
         at mid height using two LVDTs (Linear Variable Differential   table 3: compressive strength and modulus of
         Transducers) in two orthogonal directions.
                                                                rupture of concrete specimen with various RCA
                                                                percentages
                                                                   pErcEntagE       comprEssIvE      modulus of
                                                                  rEplacEmEnt       strEngth of       rupturE of
                                                                     of rca         spEcImEns In     spEcImEns In
                                                                                    mpa (28 daYs)    mpa (28 daYs)
                                                                       0%               34.12            3.98
                                                                       25%              33.48            3.86
                                                                       50%              31.81            3.49
                                                                       75%              31.19            3.09
                                                                      100%              30.48            2.74


                                                                3.1 compression tests on control and
                                                                Confined Columns
                                                                For the control column C1, the first crack was observed at a
                                                                load of 382 kN near the one- fourth height from top and bottom
                                                                extending towards middle, from left to right of the observed
                                                                face. The brittle failure occurred at an ultimate load of 531 kN.
                                                                The compression mode of failure was observed. For confined
                                                                column S1, after application of the load, the column did not
                                                                show any sign of cracking up to a load of 310 kN. As the load
                Figure 1: Reinforcement details of column specimens.
                                                                approached to 414 kN, first crack was observed in the mortar
                                                                layer with a cracking sound. The mortar layer was separated
         3. resULts AND DIscUssION
                                                                from the wire mesh with compression failure of the column near
         The details of various test results are now discussed to assess   one fourth the total height from the top. The failure of the beam
         the performance of the ferrocement confined recycled   occurred at a load of 672 kN. The maximum lateral deflection
         aggregate concrete column specimens. These test results cover   was observed as 4.61mm.
         compressive strength values of cube and modulus of rupture
         of beam specimens with replacement percentages 0%, 25%,   The control column C2 showed more deflection at lower load
         50%, 75% and 100%. Results of compression tests on control,   levels. As the load started to increase, the deflection also
         confined and retrofitted column specimens are also discussed.   increased. The first crack was observed at a load of 172 kN.